Case Study 'Fume Control Technology'

 

Client: Linatex Limited

Technology: Fume Control System

MECHON were commissioned to provide protection for employees against the harmful effects of volatile organic compounds used during the assembly process. Com-
pounds include adhesives, solvents, and cleaning agents.

Various limitations where placed on MECHON: effectiveness of fume control, noise levels, impedance of work-flow, and visual aesthetics.

Rear extract hoods where installed on two workbenches, each eleven meters long. The hoods where of similar design concept to that of fume cupboards, with rear
extraction plenum and top and side baffles. Clear acrylic sheeting was used on all baffles to maintain light levels and allow unrestricted views for employees.

The system airflow rate was calculated to attain a capture velocity of 0.35m/s across the opening of the hoods, resulting in complete fume capture towards the rear of the hoods.

A combination of using a low speed fan in an acoustic enclosure, splitter silencers on the fan inlet, and insulated ductwork on the fan outlet, ensured noise levels remained below 70dB(A).

 

<-- Back to Case Studies

 

 